Intumescent retro-fit seal for upgrading door perimeter gaps where the clearance exceeds the maximum 3mm specified by AS1905/1.

Application

Used to upgrade existing fire doors with up to and including 6mm perimeter gaps.

Key Features

  • Can provide up to 2 hours fire resistance on proprietary fire doors.
  • Non compliant fire doors can be salvaged.
  • Cost-effective solution.
  • Easy retro-fit installation.
  • Ideal for fire engineered solutions where extra protection is necessary for life safety.

Materials

Consis Twin Fin of a flame retardant PVC top hat section, encapsulating a high performance intumescent material and two rows of aggressive selfadhesive tape.

Gap Size

Up to and including 6mm perimeter gaps.

Sizes

Dimensions: 38mm x 1.6mm

Finish

Standard Colour: White and Silver
Can be painted on-site

Fixing

The KG4002 intumescent seal is simply applied to the top and sides of the door frame with two rows of aggressive self-adhesive tape. No screw fixing required.

Approval/s

  • Fire tested to AS/1530 Part 4 for up to 2 hours on proprietary fire door assemblies in accordance with AS1905 Part 1
SKU KILKG4002_
Brand Kilargo